Normal Model: NWN-60/90...1750-S-S
Cooling Tower Type: Counter Flow Closed Type
Air Ventilation:  Induced Draft ( Axial Fan Drive System)
Cooling Mode: Wet Cooling Mode
Heat Exchanger: Stainless Steel Heat Exchange Coil
Cooling Tower Body: Full- Stainless Steel SUS304/316 (NWN- Armour anti-corrosion coated steel plate for option)




NWN-S series Full- Stainless Steel Closed Type Cooling Tower
The NWN-S series cooling tower is a refined version of the NWN series counterflow closed cooling tower, featuring an enhanced anti-corrosion stainless steel frame structure for improved stability and extended service life;water saving and energy saving, high efficient and environmental frendly.
 



140x140



High-Efficiency Counter Flow Closed Circuit System

Operation
The fluid medium requiring cooling flows through the efficient serpentine coil heat exchanger, while the external spray system continuously moistens the coil surface to facilitate cooling. This allows for the exchange of heat between the cooled medium and the spray water through a partition wall heat exchanger, creating a closed loop for effective  cooling. Simultaneously, low-temperature dry air enters the tower in opposition to the spray water, with forced convection from a fan enabling counter-current heat exchange. Once fully exchanging heat, high-temperature saturated air is discharged outside of the tower, effectively reducing overall heat and lowering fluid medium temperature.



Advantage
> The counter flow close-loop circulation system guarantees the purity of the media, diminishes expenses for maintenance, and conserves precious water resources while the efficient cooling.
>
Efficient year-round cooling; enables operation without the need for spray water in winter, and has the capability to replace the chiller during winter months, resulting in a significant reduction in energy consumption.
> The
anti-corrosion stainless steel casing is designed to withstand a variety of harsh environments, while the self-draining stainless steel heat exchange coil allows for convenient anti-freeze protection during winter shutdowns.
> The product has a
compact structure and space-saving design, allowing for the combination of multiple cooling towers, without the need for pre-cooling fillers, making it ideal for cooling higher temperature working fluids.

140x140


Main Parts 

The stainless steel frame structure and shell possess exceptional anti-corrosion properties, robust heat resistance, and an exquisite appearance. The structural panels are secured with high-quality 304 stainless steel bolts.
The aluminum alloy axial flow fan is equipped with an explosion-proof motor, ensuring stable and efficient operation. The motor boasts a protection grade of IP55 and an insulation grade of F, providing enhanced safety and reliability.
Stainless steel coils exhibit superior heat exchange efficiency, enhanced corrosion resistance, light weight, prolonged equipment lifespan, and are environmentally sustainable due to their recyclability.
The exclusive drift eliminator designed for counter flow closed cooling towers is adept at efficiently extracting airborne water droplets, boasting minimal wind resistance and an impressive capture rate of 99.99%, thus guaranteeing optimal heat transfer performance.
The air inlet grille is easily detachable, featuring a special 3D three-dimensional 45-degree ventilation channel design that enhances structural strength and wind load resistance. It also boasts anti-corrosion and anti-ultraviolet properties, reduces noise, and requires no maintenance.

 


Optional Various Additional Functions

Two-speed& VFD variable frequency motor/ Vibration Cut-off Switch/ Electronic descaler/ Water treatment equipment/ Anti-freeze automatic heating system/ Noise reduction upgrade/ External maintenance platform and guardrail/Installation and maintenance boom etc.
 

140x140

Cost-effective Anti-Corrosion Solution
NWN-Armour Anti-corrosion Technology

Products coated with NWN-Armour anti-corrosion coating exhibit outstanding resistance to corrosion, approaching the qualities of stainless steel. They serve as a cost-effective alternative to stainless steel.

 
Application

Energy industry • Pharmaceutical industry • HVAC • Chemical industry • Machinery manufacturing • Metal processing • Plastic products • Industrial cooling • Food processing 


Reference Projects


NEWIN COOLING TOWER Vedio Link: https://www.youtube.com/@coolingtowernewin3278
 
300x200

Paint Factory Project 

> NWN-S series cooling tower- NEWIN cooling solution for Paint factory poject in Jiangmen, China.

300x200

NISSAN Factory Project

> NWN-S series cooling tower- NEWIN cooling solution for NISSAN factory poject in Guangzhou, China.

300x200

Paint Factory Project

> NWN-S series cooling tower- NEWIN cooling solution for Paint factory poject in Jiangmen, China.


Design Conditions

Entrance temp. t1= 37℃             Leaving temp. t2= 32℃             Wet bulb temp. tWB= 28℃             Dry bulb temp. tDB= 31.5℃              
Atmospheric pressure P0= 9.94 x 104 Pa

NWN Water Capacity Diamension (mm) Weight (kg)
Model m³/h L W H Dry Wet
NWN-60-Z7/S-S 10 1800 900 2580 650 1050
NWN-90-Z7/S-S 15 1800 900 2680 700 1100
NWN-120-Z7/S-S 20 2300 1100 2520 850 1600
NWN-180-Z7/S-S 30 2850 1100 2570 1100 2000
NWN-230-Z7/S-S 40 2850 1100 2780 1150 2100
NWN-290-Z7/S-S 50 2850 1100 2780 1250 2200
NWN-350-Z7/S-S 60 2850 1200 2940 1400 2500
NWN-450-Z7/S-S 80 4600 1450 3140 2700 3800
NWN-600-Z7/S-S 100 4600 1450 3140 2900 4100
NWN-750-Z7/S-S 125 4650 1750 3610 3400 5200
NWN-850-Z7/S-S 150 4650 2250 3740 3800 6200
NWN-1000-Z7/S-S 175 4650 2250 3910 4000 6500
NWN-1150-Z7/S-S 200 6200 2250 4020 4800 8500
NWN-1300-Z7/S-S 225 6200 2250 4020 5000 8800
NWN-1450-Z7/S-S 250 6250 2500 4280 5400 9700
NWN-1750-Z7/S-S 300 6250 3000 4380 6100 11200

This table sample only contanins the data when issued, please do not use for engineering construction. Please further to confirm with sales and engineer about the detailed data before purchasing. If need muti-cells, please consult  the manufacturer to providethe solutions. NEWIN reserves the right to change the parameters or dimensions of the table without notice.