Products
Home | F.R.P. Cooling Tower | NWQ Crosswind Cooling Tower | NWQ Crosswind cooling tower | NWQ Low Noise Crosswind Cross Flow Cooling Tower
NWQ Low Noise Crosswind Cross Flow Cooling Tower
Product Origin Guangdong
Brand NEWIN
Shipping Port Shenzhen
Color Yellow /Grey/Blue/White
Lead Time 2-6 weeks
Payment TT, L/C, West Union
Contact Now
  • Specification
  • Main parts
  • Application
  • Product Literation

Height of tower body under 3 meters, it is very suitable for installation in general building and high-rise building at technical equipment layer or middle layer, which is solved the problem of the inconvenient installation for standard cooling towers installed at the building middle layer, also makes the installation of the cooling tower easily in different area. Side inlet/outlet wind structure has installed on the position of the warm air of the cooling tower, which makes back flow of warm air greatly reduced, and improves the cooling efficiency of the cooling tower. Because installed on the middle layer, it reduces the working head of the air conditioning circulating water system, which reduces the air conditioning system of the construction costs, greatly reduce the operation cost of the system.

 


 1) Technical data of  NWQ Series Crosswind Low Noise FRP water cooling tower 


Model

Water 

Flow

 (m3/h)

Fan diameter (mm)

Weight (kg) Overall Dimension  (mm)

Water 

Pressure  

 (Kpa)

Net 

weight

Run. 

Weight

L W H
 NWQ-8 8 600 90 260 1360 820 1500 20
NWQ-10 10 600 100 270 1360 820 1500 20
NWQ-15 15 730 110 280 1360 1120 1500 20
NWQ-20 20 730 170 340 1360 1120 1500 20
NWQ-25 25 730 192 490 1870 1320 1500 26
NWQ-30 30 890 200 500 1870 1320 1960 26
NWQ-40 4 930 450 1000 1870 1320 1960 30
NWQ-80 200 1500 860 2260 2000 3200 3170 40
NWQ-100 225 1500 1060 2460 2500 3200 3170 40
NWQ-125 250 1800 1280 3030 3000 3200 3170 42
NWQ-150 300 2100 1380 3750 3250 3500 3170 42
NWQ-175 350 2100 1500 4010 3750 3500 3170 47
NWQ-200 400 2400 1800 4220  3750 3500 3770 47
NWQ-225 450 2400 1910 4350 4000 3500 3770 53
NWQ-250 500 2400 2580 5480 4500 3500 3770 53


 2) Foundation of NWQ series crosswind square type FRP water cooling tower 


Model

L  (mm)

L1   (mm)

W (mm)

W1   (mm)

W2 (mm)

NWQ-8

830

 

650

 

 

NWQ-10

830

 

650

 

 

NWQ-15

830

 

850

 

 

NWQ-20

830

 

850

 

 

NWQ-25

1340

 

1050

 

 

NWQ-30

1340

 

1050

 

 

NWQ-40

1340

 

1050

 

 

NWQ-80

2260

1960

2750

950

1500

NWQ-100

2760

2460

2750

950

1500

NWQ-125

3260

2960

2750

950

1500

NWQ-150

3510

3210

2950

1150

1500

NWQ-175

4010

3710

2950

1150

1500

NWQ-200

4010

3710

 2950

1150

1500

NWQ-225

4260

3960

2950

1150

1500

NWQ-250

4760

4460

2950

1150

1500

 

 

 3) Pipeline of NWQ Crosswind Cross Flow F.R.P Cooling Tower

 

Model

Inlet  (mm)

Outlet

(mm)

Overflow

 (mm)

Drain

 (mm)

Quick feeding 

(mm)

 Auto. 

feeding 

(mm)

NWQ-8

40

40

25

25

15

 

NWQ-10

40

40

25

25

15

 

NWQ-15

50

50

25

25

15

 

NWQ-20

50

50

25

25

15

 

NWQ-25

80

80

25

25

15

 

NWQ-30

80

80

25

25

15

 

NWQ-40

80

80

25

25

15

 

NWQ-80

125

125

80

80

25

40

NWQ-100

125

125

80

80

25

40

NWQ-125

150

150

80

80

25

40

NWQ-150

150

150

80

80

25

40

NWQ-175

125 x 2

200

80

80

25

40

NWQ-200

150 x 2

200

80

80

25

40

NWQ-225

150 x 2

200

80

80

25

40

NWQ-250

150 x 2

250

80

80

25

40

 

under construction
under construction
under construction
Recently Viewed Products
  • 300RT open circuit cooling tower Counter Flow Round Type Cooling Tower NRT-300

    NRT series cooling towers' performance was strictly examined by "Quality Supervision and Inspection Center of National Glass work" in 2006, the result showed NRT series cooling towers completely comply with all national standards.   Design Features NRT series counter flow induced draft cooling tower is designed with bottle type structure, So that the volume of prevailing air is minimized. Every part of the cooling tower is designed and made precisely and further permits easy installation and endurance due to light weight and strong structure. The testing report of cooling capacity proves its high efficiency.   Casing and Water Basin Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements.Fiberglass reinforced polyester(FRP) is applied with water-resistance resin and high quality fiberglass mat. With good moisture, high gel,high strength, spray the gel-coat on FRP parts by machine and is thermal formed. The surface is as smooth as mirror and could resist ultraviolet radiation. Also, it is colorfast and durable.   Fan Blades Aluminum alloy axial flow fan with adjustable pitch blades are applied and being balanced so that it can operation stably and quietly. Blades of fan can be adjusted according to the requirement of air volume.To assure that the maximum effective of exhausting air.     Fan Drive Small capacity cooling tower adopts direct drive low noise fan. Bigger capacity fan equipped with Belt drive speed reducer. Adjust belt tension through automatic spring to save the manual maintenance. Total enclosed structure can assure the low noise operation. This series of cooling tower have passed the GB7190.1-1997 quality certification of supper low noise. Further more the belt is durable without negative effect from water vapor and sunshine.   Water Distribution   The using of high coefficient rotating sprinkler heads made of reinforced plastic or aluminum alloy can reduce the pressure of friction loss. Besides, the water can be distributed evenly to achieve the max thermal performance.       Infill    Standard and low noise cooling tower are using high class thermal formed PVC sheet. The sheets are added with industrial plaits material and long fiberglass to slow the aging and increase the strength. Moreover the water film is thinner and longer so that the infill cabbage coefficient is higher. The infill is formed in the factory, instead of at construction site. To avoid uneven problem during installing. And it cold be easily cleaned and maintained in future. High temperature cooling tower is using P.P. Infill that could withstand up to 90 degreeC water temperature. The surface of such infill is corrugated to increase the filling pitch to make sure that infill is clog-free and overcome the problem of water quality.    

  • cross/mixed flow closed circuit cooling tower LKH-150 cross/mixed flow closed circuit cooling tower LKH-150

    1.Water processing capacity: 150m3/ h 2.△t = 5℃( Inlet37℃, outlet 32℃ ) 3. Design wet bulb temperature:28℃ Warranty, and after service. 1.Warranty period:12 month. Any damage caused by supplier, should provide free technical service, and free replacement parts; 2.Engineer should be send by supplier for installing and commissioning.

  • NTS Counter Flow Turbine Drive Cooling Tower NTS Counter Flow Turbine Drive Cooling Tower

    Components Instruction Infill  Specially designed S shape PVC infill is vacuum formed of 0.3 thickness or more thicker PVC film with excellent chemical and high distortion resistance, big coefficient of heat transfer, small wind resistance, high ventilation performance. We have different materials like PVC, UPVC, and PP  to suit different water temperature.  Drift Eliminator The NSH series cooling tower used easy installed PVC material drift eliminator to prevent water from splashing out of the cooling tower.   Steel Structure  Hop-dip galvanized steel framework to keep the cooling tower great performance and long lifespan, good anti-corrosion, guarantee the use of more than 15 years. Stainless steel hardware parts are also available for options if somewhere special condition needed.   Air Inlet Louver The air inlet louver is used of F.R.P parts which makes the long life of the whole cooling tower. For sewage water cooling tower, we will use different type of the air inlet louver to meet customers requirements. Distribution Nozzles The distribution nozzles used high quality A.B.S /PP material, easy to installed on the water pipe and make sure the water splashed evenly on the infill.     Technical Data of NTS Series Counter Flow Turbine Cooling Tower Model Water  Flow  (m3/h)  Fan Diameter Weight (kg) Overall Dimension  (mm) Water  Pressure    (Kpa) Net  weight Run.  Weight L W H  NTS-100-1 100 1500 1130 2230 2200 2200 4670 145 NTS-125-1 125 1800 1190 2300 2000 2200 4670 145 NTS-150-1 150 1800 1540 2970 2800 2800 4670 145 NTS-175-1 175 2100 1620 3040  2800 2800 4670 145 NTS-200-1 200 2100 1970 4330 3200 3200 4670 150 NTS-225-1 225 2400 2110 4460 3200 3200 4670 150 NTS-250-1 250 2400 2260 4520 3600 3600 4670 160 NTS-300-2 300 1800 2380 4600 5600 2800 4670 145 NTS-350-2 350 2100 2650 5390 5600 2800 4670 145 NTS-400-2 400 2100 3080 5940 6400 3200 4670 150 NTS-450-2 450 2400 3240 6080 6400 3200 4670 150 NTS-500-2 500 2400 3940 8660 7200 3600 4670 160 NTS-525-3 525 2100 4860 9120  8400 2800 4870 150 NTS-600-3 600 2100 5910 12990 9600 3200 4870 160 NTS-700-4 700 2100 6480 12160  11200 2800 4870 150 NTS-800-4 800 2100 7880 17320 12800 3200 4870 160 NTS-900-4  900  2400 8440 18080 12800   3200  4870 160   NTS-1000-4  1000  2100  10600 21560  14400   3600  4870 170    Remark:   1. Working condition: dry bulb temp.=31.5℃, wet bulb temp.=28℃, inlet water=37℃, outlet water=32℃, atmospheric pressure=99.4Kpa.   2. When installing pipeline of the cooling towers, Y-strainers, valves and pressure gauges are needed at the water inlet pipe.   3. Keep foundation surface level, error limit ±5mm.   4. Special design for other model are acceptable by technical department.  

  • Newin Small Round Cooling Water Tower NRT-15 Newin Small Round Cooling Water Tower NRT-15

    NRT series cooling towers' performance was strictly examined by "Quality Supervision and Inspection Center of National Glass work" in 2006, the result showed NRT series cooling towers completely comply with all national standards.   Design Features NRT series counter flow induced draft cooling tower is designed with bottle type structure, So that the volume of prevailing air is minimized. Every part of the cooling tower is designed and made precisely and further permits easy installation and endurance due to light weight and strong structure. The testing report of cooling capacity proves its high efficiency.   Casing and Water Basin Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements.Fiberglass reinforced polyester(FRP) is applied with water-resistance resin and high quality fiberglass mat. With good moisture, high gel,high strength, spray the gel-coat on FRP parts by machine and is thermal formed. The surface is as smooth as mirror and could resist ultraviolet radiation. Also, it is colorfast and durable.   Fan Blades Aluminum alloy axial flow fan with adjustable pitch blades are applied and being balanced so that it can operation stably and quietly. Blades of fan can be adjusted according to the requirement of air volume.To assure that the maximum effective of exhausting air.     Fan Drive Small capacity cooling tower adopts direct drive low noise fan. Bigger capacity fan equipped with Belt drive speed reducer. Adjust belt tension through automatic spring to save the manual maintenance. Total enclosed structure can assure the low noise operation. This series of cooling tower have passed the GB7190.1-1997 quality certification of supper low noise. Further more the belt is durable without negative effect from water vapor and sunshine.   Water Distribution   The using of high coefficient rotating sprinkler heads made of reinforced plastic or aluminum alloy can reduce the pressure of friction loss. Besides, the water can be distributed evenly to achieve the max thermal performance.       Infill    Standard and low noise cooling tower are using high class thermal formed PVC sheet. The sheets are added with industrial plaits material and long fiberglass to slow the aging and increase the strength. Moreover the water film is thinner and longer so that the infill cabbage coefficient is higher. The infill is formed in the factory, instead of at construction site. To avoid uneven problem during installing. And it cold be easily cleaned and maintained in future. High temperature cooling tower is using P.P. Infill that could withstand up to 90 degreeC water temperature. The surface of such infill is corrugated to increase the filling pitch to make sure that infill is clog-free and overcome the problem of water quality.    

  • 400m³/h cross flow cooling tower cross flow cooling tower NST-400

    Features of NEWIN square type cross flow cooling tower Space saving, light-duty structures Using specially designed infill which ensure high efficient heat transferring, heat transfer area increased significantly, smaller installing area, due to the optimization design of steel structure, operating weight greatly reduced accordingly. Energy saving Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements. Low noise Special designed low noise FRP/aluminum alloy material wing type axial flow fan and motor, so as to reduce the running noise of cooling tower. Lower running noise for super low noise models, fully meet the environmental friendly requirements. If double speed motor running at low speed in the night, the noise can go down by 2 to 3 db (A). The user who needs double speed motor please comment when placing the order. Good corrosion resistance Tower casing, tank and panel are make up of high corrosion resistance performance FRP material, adding light stabilizer to the gel coating to make it good anti-aging performance and not fade. Galvanized steel structure to improve the corrosion resistance performance of the cooling tower, no need additional anti-corrosion within normal service life. Convenient combination Combinations can be used to meet the requirements of different working conditions, users can decide combine or not according to the field situation. What’s more, adjust the cooling tower combination appearance according to surrounding buildings’ structure characteristics. If limited space in end user, our company can also design for the special cooling tower to meet users’ requirements for the performance of thermal and noise. Easy maintenance This series of cooling towers are modular design, air chamber of adjacent cooling towers are separated from each other, maintenance, packing cleaning, pipe cleaning, water tank cleaning can be done under cooling tower normal working.

Copyright © Shenzhen Newin Machinery Co., Ltd.All Rights Reserved.