Cross flow closed circuit cooling tower

LKH-30 specification

 

I. Design Condition

Water processing capacity: 30 m3/ h

△t = 5℃ ( Inlet 37, outlet 32℃ ) 

        Design wet bulb temperature28℃ 

        Design dry bulb temperature: 31.5℃ 

        Atmosphere: 99,400Pa

D

II. Selection Model

   Closed circuit cross flow cooling tower 

   Model: LKH-30

 

III. Cooling tower performance data sheet(single cell) 

 

Model

LKH-30

Water flow rate

30m3/ h

Temperature in

37℃

Temperature out

32℃(2-5℃ above WBT in summer)

WTB

28℃

Temperature decrease

5℃

heat exchanging capacity

150,000 kcal/h

Power

3φ-400V/50Hz

Total power

3.7kW

Drift loss

0.005%

Noise level

Not more than 75dB(A) 

According to GB9068 measurement

     Axial fan

Quantity

2 sets

Air volume

32000m3/ h

Power

1.1Kwx2

Speed

720r/min

Air pressure

140pa

  Spray pump

Quantity

1set

Water volume

32.5 m3/ h

Power

1.5Kw

Coil pressure

1.2Mpa

Water Resistance

80KPa

Inlet pipe diameter

DN80

Outlet pipe diameter

DN80

    dimension

Length

2500 mm

Width

1970 mm

Height

2263 mm

       Weight

Net weight (kg)

850

Operation weight (kg)

3100

 

 ※ We reserve the right to modify the above information without further notice.

Components list


No.

Name

Qty

Specification

Origin

Performance

1

Coil cooler

(coil type)

set

 

2

copper tube

Φ16mm 

δ=0.65mm

shanghai

 

 

2

Casing

set

1

δ= 2mm

Shanghai

high strength galvanized steel,

The material is composed of aluminum, 

zinc, such as silicon, has a good anti-corrosive and insulating performance, 

service life is 3 to 6 times that of the 

normal 

galvanized sheet.

3

Water basin

set

1

δ= 2mm

Shanghai

4

Eliminator

set

1

PVC

Dongguan

Spray water loss <0.5%

5

Infill

set

1

PVC

Dongguan

Pure PVC

6

Fan blades

set

4

Aluminum alloy

Dongguan

high-strength aluminum alloy

7

Fan motor

set

4

Cast iron

Dongguan

ABB brand

IP55, TEFC

8

Bearing

set

4

NTN

Japan

Oil free, Japan imported

9

Air duct

Pic

4

Galvanized steel

Dongguan

Height 500 mm, protection cover,

10

Spray pump

set

1

In-line pump

Dongguan

Big flow,small head, water-prof, cooling tower specialize

11

Spray pump motor

set

 

1

Total closed

Dongguan

 Executive Standard JIS-C4210,

IP54, Class F

12

Motor Bearing

set

1

NTN

Japan

Oil free

13

Spray pipe

set

1

Galvanized steel

 

 

14

Spray head

set

/

ABS type spiral nozzle

Shanghai

With pray balance tank

15

Water level control

pic

1

SUS float valve

Shanghai

Auto-feed water

16

Drain outlet

pic

1

SUS ball valve

Shanghai

 

17

Inlet&outlet

set

2

SUS Flange

Shanghai

 

18

Air-inlet grille

Pic

6

PVC or 

aluminum zinc plate

Shanghai

 

Application Industries:


  · High frequency power source capacitance

 

· Furnace

 

· Quenching water/oil tank


 

 · Hydraulic pressure station



· Pressing machine


 

 · Air compressor



· Central air-conditioning system


 

· Power generato


 

Drawing and parameters:


Technical specification of cooling tower LKH-30  1cell unit

Outline dimension drawing of cooling tower LKH-30  1cell unit


Note: 

The list technical details shall not be binding unless confirmed in writing by NEWIN. 

We reserve the rights to modify the technical details without further notice.
Recently Viewed Products
  • Saudi cooling tower 500RT Counter Flow Round Type Cooling Tower NRT-500

    NRT series cooling towers' performance was strictly examined by "Quality Supervision and Inspection Center of National Glass work" in 2006, the result showed NRT series cooling towers completely comply with all national standards.   Design Features NRT series counter flow induced draft cooling tower is designed with bottle type structure, So that the volume of prevailing air is minimized. Every part of the cooling tower is designed and made precisely and further permits easy installation and endurance due to light weight and strong structure. The testing report of cooling capacity proves its high efficiency.   Casing and Water Basin Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements.Fiberglass reinforced polyester(FRP) is applied with water-resistance resin and high quality fiberglass mat. With good moisture, high gel,high strength, spray the gel-coat on FRP parts by machine and is thermal formed. The surface is as smooth as mirror and could resist ultraviolet radiation. Also, it is colorfast and durable.   Fan Blades Aluminum alloy axial flow fan with adjustable pitch blades are applied and being balanced so that it can operation stably and quietly. Blades of fan can be adjusted according to the requirement of air volume.To assure that the maximum effective of exhausting air.     Fan Drive Small capacity cooling tower adopts direct drive low noise fan. Bigger capacity fan equipped with Belt drive speed reducer. Adjust belt tension through automatic spring to save the manual maintenance. Total enclosed structure can assure the low noise operation. This series of cooling tower have passed the GB7190.1-1997 quality certification of supper low noise. Further more the belt is durable without negative effect from water vapor and sunshine.   Water Distribution   The using of high coefficient rotating sprinkler heads made of reinforced plastic or aluminum alloy can reduce the pressure of friction loss. Besides, the water can be distributed evenly to achieve the max thermal performance.       Infill    Standard and low noise cooling tower are using high class thermal formed PVC sheet. The sheets are added with industrial plaits material and long fiberglass to slow the aging and increase the strength. Moreover the water film is thinner and longer so that the infill cabbage coefficient is higher. The infill is formed in the factory, instead of at construction site. To avoid uneven problem during installing. And it cold be easily cleaned and maintained in future. High temperature cooling tower is using P.P. Infill that could withstand up to 90 degreeC water temperature. The surface of such infill is corrugated to increase the filling pitch to make sure that infill is clog-free and overcome the problem of water quality.    

  • LKM-N Series Compact Unit Closed Circuit Cooling Tower LKM-N Series Compact Unit Closed Circuit Cooling Tower

      Compact unit closed circuit cooling tower is a type of cooling tower which compact with counter flow closed circuit cooling tower, buffer water tank, circulating water pump, pipes, control cabinet and filter system(options). The compact design makes cooling tower can independent working with out any other auxiliary equipment. Because of the compact design, Fully functional, easy installation, the cooling tower are widely used in different industries. Due to big size of compact unit. At present, the compact unit closed circuit cooling tower could only suite for cooling tower capacity below 60m³/h.          Technical parameters of LKM-N series closed circuit cooling tower          Item Water  Flow  (m3/hr) Fan Spray Pump Inlet/Outlet  Pipe Dia.  (mm) Weight (kg) Dimension          Model Air Volume   (m3/hr) Power  (KW) Flow  (m³/hr) Power  (KW) Net Weight Run. Weight L×W×H  (mm) LKM-N5 5 10500 0.55 14 0.75 50 T:350 600 2150x900x1920 LKM-N8 8 13050 0.75 14 0.75 65 T:400 700 2150x1150x1920 LKM-N10 10 26100 0.75*2 30 1.1 65 T:520 1000 2400x1150x2200 LKM-N15 15 26100 0.75*2 30 1.1 65 T:570 1100 2400x1150x2200 LKM-N20 20 36600 1.1*2 40 1.5 80 T:650 1600 2400x1150x2200 LKM-N25 25 36600 1.1*2 40 1.5 80 T:750 1700 3600x1150x2350 LKM-N35 35 40600 1.5*2 40 1.5 80 T:850 1800 3600x1400x2650 LKM-N40 40 40600 1.5*2 60 1.5 100 T:1050 2000 3600x1400x2650 LKM-N50 50 46900 2.2*2 60 1.5 100 T:1250 2300 3600x1400x2650 LKM-N60 60 53000 2.6*2 60 1.5 100 T:1350 2400 3600x1400x2650 Note:  1. Design condition: Wet bulb temp. 28°C, standard temperature difference is 5°C.                                                                                               2. All cooling coil connection is approximate position, we will change according to actual working condition.                                                  3. We reserve the right to modify the above information without further notice.     

  • 250m³/h cross flow cooling tower Cross Flow Cooling Tower NST-250

    Features of NEWIN square type cross flow cooling tower Space saving, light-duty structures Using specially designed infill which ensure high efficient heat transferring, heat transfer area increased significantly, smaller installing area, due to the optimization design of steel structure, operating weight greatly reduced accordingly. Energy saving Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements. Low noise Special designed low noise FRP/aluminum alloy material wing type axial flow fan and motor, so as to reduce the running noise of cooling tower. Lower running noise for super low noise models, fully meet the environmental friendly requirements. If double speed motor running at low speed in the night, the noise can go down by 2 to 3 db (A). The user who needs double speed motor please comment when placing the order. Good corrosion resistance Tower casing, tank and panel are make up of high corrosion resistance performance FRP material, adding light stabilizer to the gel coating to make it good anti-aging performance and not fade. Galvanized steel structure to improve the corrosion resistance performance of the cooling tower, no need additional anti-corrosion within normal service life. Convenient combination Combinations can be used to meet the requirements of different working conditions, users can decide combine or not according to the field situation. What’s more, adjust the cooling tower combination appearance according to surrounding buildings’ structure characteristics. If limited space in end user, our company can also design for the special cooling tower to meet users’ requirements for the performance of thermal and noise. Easy maintenance This series of cooling towers are modular design, air chamber of adjacent cooling towers are separated from each other, maintenance, packing cleaning, pipe cleaning, water tank cleaning can be done under cooling tower normal working.

  • 100m³/h cross flow cooling tower cross flow cooling tower NST-100

    Features of NEWIN square type cross flow cooling tower Space saving, light-duty structures Using specially designed infill which ensure high efficient heat transferring, heat transfer area increased significantly, smaller installing area, due to the optimization design of steel structure, operating weight greatly reduced accordingly. Energy saving Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements. Low noise Special designed low noise FRP/aluminum alloy material wing type axial flow fan and motor, so as to reduce the running noise of cooling tower. Lower running noise for super low noise models, fully meet the environmental friendly requirements. If double speed motor running at low speed in the night, the noise can go down by 2 to 3 db (A). The user who needs double speed motor please comment when placing the order. Good corrosion resistance Tower casing, tank and panel are make up of high corrosion resistance performance FRP material, adding light stabilizer to the gel coating to make it good anti-aging performance and not fade. Galvanized steel structure to improve the corrosion resistance performance of the cooling tower, no need additional anti-corrosion within normal service life. Convenient combination Combinations can be used to meet the requirements of different working conditions, users can decide combine or not according to the field situation. What’s more, adjust the cooling tower combination appearance according to surrounding buildings’ structure characteristics. If limited space in end user, our company can also design for the special cooling tower to meet users’ requirements for the performance of thermal and noise. Easy maintenance This series of cooling towers are modular design, air chamber of adjacent cooling towers are separated from each other, maintenance, packing cleaning, pipe cleaning, water tank cleaning can be done under cooling tower normal working.

  • 1000m³/h cross flow cooling tower cross flow cooling tower NST-1000

    Features of NEWIN square type cross flow cooling tower Space saving, light-duty structures Using specially designed infill which ensure high efficient heat transferring, heat transfer area increased significantly, smaller installing area, due to the optimization design of steel structure, operating weight greatly reduced accordingly. Energy saving Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements. Low noise Special designed low noise FRP/aluminum alloy material wing type axial flow fan and motor, so as to reduce the running noise of cooling tower. Lower running noise for super low noise models, fully meet the environmental friendly requirements. If double speed motor running at low speed in the night, the noise can go down by 2 to 3 db (A). The user who needs double speed motor please comment when placing the order. Good corrosion resistance Tower casing, tank and panel are make up of high corrosion resistance performance FRP material, adding light stabilizer to the gel coating to make it good anti-aging performance and not fade. Galvanized steel structure to improve the corrosion resistance performance of the cooling tower, no need additional anti-corrosion within normal service life. Convenient combination Combinations can be used to meet the requirements of different working conditions, users can decide combine or not according to the field situation. What’s more, adjust the cooling tower combination appearance according to surrounding buildings’ structure characteristics. If limited space in end user, our company can also design for the special cooling tower to meet users’ requirements for the performance of thermal and noise. Easy maintenance This series of cooling towers are modular design, air chamber of adjacent cooling towers are separated from each other, maintenance, packing cleaning, pipe cleaning, water tank cleaning can be done under cooling tower normal working.

Copyright © Shenzhen Newin Machinery Co., Ltd.All Rights Reserved.