1)  Technical data of circular type cooling tower NRT-300

Item

Content

Parameter

Basic data

 

 Type

Counter-flow round type

 Model

NRT-300

 Water flow

234 m3/h

 Inlet/outlet temperature

37°C/32°C

 Dry/Wet bulb temperature

31.5°C /27°C

 Cooling capacity

1,171,200 kcal/h

 Power supply

380V3Ph/50Hz

 Water quality

PH=6-8

Design data

 Air/water ratio

0.62 kg/kg

 Drift loss

≤0.02%

 Evaporating loss

≤0.833%

 Net weight

1760 kg

 Running weight

3930 kg

Fan data

 Fan type

Axial-flow 

 Air flow

128,700 m3/h

 Fan rotate speed

275 r/min

 Diameter (F)

2400 mm

 Blade quantity

 4 pcs/set

 Type of drive

Vee belt

 Motor rotate speed

1410 r/min

 Motor power

7.5 kW

 Motor starting method

Y-△

Dimension

 Tower diameter (F)

4730 mm

 Tower height (H)

3680 mm

 Inlet/outlet pipe dimension (DN)

200 mm200 mm

 Full/drain pipe dimension (DN)

80 mm80 mm

 Quick feed pipe dimension (DN)

40 mm


2) Overall dimension of bottle type cooling tower NRT-300

 

3) Foundation of round type cooling tower NRT-300

  

※ We reserve the right to modify the above information without further notice.

The Main parts of cooling tower consists of motor, fan, infill, sprinkler system, F.R.P parts, etc. We use great quality of the cooling tower parts to make sure the great performance and long lifespan of the Newin cooling towers. If customers have other special requirements for the cooling tower, we will try our best to satisfy their needs.

 

       
       

 

Parts  Material  Remark

Water Basin

 F.R.P Water-resistance resin and high quality fiberglass mat

 Casing

 F.R.P Water-resistance resin and high quality fiberglass mat
 Motor  Cast Iron Fully enclosed anti water type, other brand motors for optional
 Motor support  Hot dip galvanized  steel  In accordance with BS EN ISO1461:1999 standard

 Fan

 Alum alloy stainless steel for optional 

 Infill

 P.V.C  film For high temperature inlet water, UPVC and PP material for optional

 Air inlet screen  

 P.V.C   F.R.P  for optional

 Sprinkler head

 A.B.S  Aluminum alloy material for optional

 Sprinkler pipe

 P.V.C  For high temperature inlet water, hot-dip galvanized steel for optional

 Bolts & Nuts 

 Electroplated   Stainless steel 304, 316 for optional






















Cooling tower is mainly used in air conditioning cooling system, frozen industry, injection molding, tanning, foaming, electricity, steam turbine, aluminum processing, air compressors, industrial water cooling, etc.  Those industries  could be divided into 4 categories as follows:
♦  Air temperature adjust : air conditioning, refrigerator, freezer, refrigeration, air conditioning, etc.;
♦  Manufacturing and processing: the food industry, pharmaceutical industry, metal casting, plastic industry, rubber industry, textile industry, steel mills, chemical industry, petrochemical products, etc.;
♦ Cooling the running machines: mechanical operation of the generator, steam turbine, air compressor, hydraulic press, engine, etc.;
♦  other industries...

 

Below is some round type cooling towers' project in different industries.

   
   
   
   

Drawing and parameters:


Technical specification of cooling tower NRT-300

Outline dimension drawing of cooling tower NRT-300

Foundation size and construction drawing of cooling tower NRT-300


Note: 

The list technical details shall not be binding unless confirmed in writing by NEWIN. 

We reserve the rights to modify the technical details without further notice.
Recently Viewed Products
  • cross flow closed circuit cooling tower LKM-125 cross flow closed circuit cooling tower LKM-125

    LKM series closed circuit cooling tower is a kind of high efficient heat exchange equipment which comes into being on the basis of absorbing the most advanced foreign heat-exchange technology.  The Air intake style is inlet from the bottom of the tower, which is alternating direction interactive with the fall down spray water and from to saturated vapor in the process. The heat is exhausted out of tower by the fan and the water is collected to bottom tank and circulate continuously by the special evaporator. There is no heat sinking fillings inside of the tower, so more space is saved to increase coil area. This apply especially to suit for smaller fluid cooling fluid in low temperature or small temperature difference.     Technical parameters of LKM series closed circuit cooling tower          Item  Water Flow (m3/h) Fan Spray Pump Inlet/Outlet  Pipe Dia.  (mm) Weight (kg) Dimension          Model Air Volume   (m3/h) Power  (KW) Flow  (m³/h) Power  (KW) Net Weight Run. Weight L×W×H      (mm) LKM-5 5 10500 0.55 14 0.75 50 T:350 600 1150x900x1920 LKM-8 8 13050 0.75 14 0.75 65 T:400 700 1150x1150x1920 LKM-10 10 26100 0.75*2 30 1.1 65 T:520 1000 2000x1150x2200 LKM-15 15 26100 0.75*2 30 1.1 65 T:570 1100 2000x1150x2200 LKM-20 20 36600 1.1*2 40 1.5 80 T:650 1600 2500x1150x2200 LKM-25 25 36600 1.1*2 40 1.5 80 T:750 1700 2500x1150x2350 LKM-35 35 40600 1.5*2 40 1.5 80 T:850 1800 2500x1400x2650 LKM-40 40 40600 1.5*2 60 1.5 100 T:1050 2000 2500x1400x2650 40600 1.5*2 60 1.5 100 G:2150 3000 3000x1400x2650 LKM-50 50 46900 2.2*2 60 1.5 100 T:1250 2300 2500x1400x2650 46900 2.2*2 60 1.5 100 G:2450 3500 3000x1400x2650 LKM-60 60 53000 2.6*2 60 1.5 100 T:1350 2400 2500x1400x2650 53000 2.6*2 60 1.5 100 G:2650 3700 3000x1400x2650 LKM-70 70 63800 3.5*2 65 2.2 100 T:1650 3000 3000x1400x2850 63800 3.5*2 65 2.2 100 G:2950 4300 3518x1400x3310 LKM-80 80 90000 4*2 65 2.2 125 T:1850 3300 3000x1400x2850 90000 4*2 65 2.2 125 G:3560 5000 3518x2180x3310 LKM-100 100 90000 4*2 110 3 125 T:2050 3800 3000x2180x2850 90000 4*2 110 3 125 G:4150 5900 3518x2180x3310 LKM-125 125 110000 5.5*2 110 3 100*2 T:2450 4300 3518x2180x3250 110000 5.5*2 110 4 100*2 G:5150 7000 4010x2180x3910 LKM-150 150 150000 7.5*2 110 3 100*2 T:3150 4300 3518x2180x2850 150000 7.5*2 140 4 100*2 G:6500 8100 4010x2980x3910 LKM-175 175 180000 7.5*2 170 5.5 100*2 T:3700 7100 4010x2980x3910 180000 7.5*2 220 7.5 100*2 G:7120 10500 5380x2980x3910 LKM-200 200 220000 7.5*2 170 5.5 125*2 T:4180 7600 4010x2980x3910 220000 7.5*2 220 7.5 125*2 G:8300 11700 5380x2980x3910 LKM-250 250 300000 11*2 170 5.5 125*2 T:5050 8900 4510x2980x3910 300000 11*2 220 7.5 125*2 G:10680 14600 5380x2180x3910 LKM-300 300 300000 7.5*4 220 3*2 100*4 T:6300 8600 7036x2180x2850 300000 7.5*4 220 3*2 100*4 G:12100 16200 8020x2980x3910 LKM-350 350 360000 7.5*4 340 5.5*2 125*4 T:7400 14200 8020x2980x3910 360000 7.5*4 440 7.5*2 125*4 G:14240 21000 107600x2980x3910 LKM-400 400 440000 7.5*4 340 5.5*2 125*4 T:8360 15200 8020x2980x3910 440000 7.5*4 440 7.5*2 125*4 G:16600 23400 107600x2980x3910 LKM-500 500 600000 11*4 340 5.5*2 125*4 T:10100 17800 8020x2980x3910 600000 11*4 440 7.5*2 125*4 G:21360 29200 107600x2980x3910  ※ We reserve the right to modify the above information without further notice.

  • 600RT counter flow cooling tower Counter Flow Round Type Cooling Tower NRT-600

    NRT series cooling towers' performance was strictly examined by "Quality Supervision and Inspection Center of National Glass work" in 2006, the result showed NRT series cooling towers completely comply with all national standards.   Design Features NRT series counter flow induced draft cooling tower is designed with bottle type structure, So that the volume of prevailing air is minimized. Every part of the cooling tower is designed and made precisely and further permits easy installation and endurance due to light weight and strong structure. The testing report of cooling capacity proves its high efficiency.   Casing and Water Basin Adopting small ventilation resistance packing and special designed FRP/aluminum alloy high efficiency fan, greatly reduced the motor power. Smaller motor power are designed for low noise model, save more power, double speed motor for optional to power saving according to customers’ special requirements.Fiberglass reinforced polyester(FRP) is applied with water-resistance resin and high quality fiberglass mat. With good moisture, high gel,high strength, spray the gel-coat on FRP parts by machine and is thermal formed. The surface is as smooth as mirror and could resist ultraviolet radiation. Also, it is colorfast and durable.   Fan Blades Aluminum alloy axial flow fan with adjustable pitch blades are applied and being balanced so that it can operation stably and quietly. Blades of fan can be adjusted according to the requirement of air volume.To assure that the maximum effective of exhausting air.     Fan Drive Small capacity cooling tower adopts direct drive low noise fan. Bigger capacity fan equipped with Belt drive speed reducer. Adjust belt tension through automatic spring to save the manual maintenance. Total enclosed structure can assure the low noise operation. This series of cooling tower have passed the GB7190.1-1997 quality certification of supper low noise. Further more the belt is durable without negative effect from water vapor and sunshine.   Water Distribution   The using of high coefficient rotating sprinkler heads made of reinforced plastic or aluminum alloy can reduce the pressure of friction loss. Besides, the water can be distributed evenly to achieve the max thermal performance.       Infill    Standard and low noise cooling tower are using high class thermal formed PVC sheet. The sheets are added with industrial plaits material and long fiberglass to slow the aging and increase the strength. Moreover the water film is thinner and longer so that the infill cabbage coefficient is higher. The infill is formed in the factory, instead of at construction site. To avoid uneven problem during installing. And it cold be easily cleaned and maintained in future. High temperature cooling tower is using P.P. Infill that could withstand up to 90 degreeC water temperature. The surface of such infill is corrugated to increase the filling pitch to make sure that infill is clog-free and overcome the problem of water quality.    

  • Box Type Cooling Tower NSH-350 Box Type Cooling Tower NSH-350

    NSH series counter flow square type cooling tower is available in capacity for single cell from 40 tons to 1000 tons, various modular combinations of cooling towers are designed to meet different requirements. This type of cooling tower is mainly used in heating, ventilation, air-conditioning, and light to medium processing applications.

  • counter flow cooling tower Square Type Cooling Tower NSH-175

    NSH Series Counter flow Fiberglass Reinforced Plastic Square Type cooling towers uses counter flow air heat exchange technology, the cooling tower packing / cooling tower infill is made of high quality modified polyvinyl chloride (PVC) wave plate, to spread  the drench water area, and adopts fixed water sprinkling system, selection of ABS low pressure water spray nozzle, uniform water distribution, long service life, and with low water head, to save water distribution power system.

  • cross/mixed flow closed circuit cooling tower LKH-100 cross/mixed flow closed circuit cooling tower LKH-100

    1.Water processing capacity: 100m3/ h 2.△t = 5℃( Inlet37℃, outlet 32℃ ) 3. Design wet bulb temperature:28℃ Warranty, and after service. 1.Warranty period:12 month. Any damage caused by supplier, should provide free technical service, and free replacement parts; 2.Engineer should be send by supplier for installing and commissioning.

Copyright © Shenzhen Newin Machinery Co., Ltd.All Rights Reserved.